MODEM-PT (Modem Pool Port)
Issue 1 May 2002
8-1145555-233-143
2323 ABORT The Maintenance Test circuit pack digital port allocated for this test did not
disconnect properly. This error is more closely related to the Maintenance Test
circuit pack digital port used for this test than the TN758 Pooled Modem circuit
pack itself. Therefore, any hardware testing or replacement activities will focus
on the Maintenance Test circuit pack.
1. Wait 1 minute and attempt the test again up to 5 times.
2324 ABORT The digital portion of the tested Modem Pool port did not disconnect properly.
1. Wait 1 minute and attempt the test again.
2. If the test continues to abort, replace the Pooled Modem circuit pack and
retest.
2325 FAIL The Modem Pool port did not respond with an on-hook message when the
connection to the TN711 Maintenance/Test digital port was broken, indicating a
likely problem with the TN758 Pooled Modem circuit pack.
1. Busyout both of the TN758 Pooled Modem conversion resources on the
circuit pack containing the failing conversion resource.
2. If the test continues to fail, replace the Pooled Modem circuit pack and
retest.
FAIL The Loop-around test failed, the loop-back data did not match the original data.
1. Repeat Test #98.
2. If the test fails again, replace the Pooled Modem circuit pack.
PASS The port can correctly transmit/receive data.