Maintenance-Object Repair Procedures
555-233-143
8-1184 Issue 1 May 2002
Error Log Entries and Test to Clear Values
Notes:
a. This is a software audit error that does not indicate any hardware
malfunction. Run the short test sequence, and investigate associated
errors (if any).
b. The DS1 OPS Line has been busied out by a busyout station ext
command. No calls can be made on this line.
c. This error type indicates that the circuit pack has been removed or has
been insane for more than 11 minutes. To clear the error, reinsert or
replace the circuit pack.
d. Error Type 1793 indicates a problem with the DS1 Interface circuit pack.
Since there is no error against the OPS-LINE port, no alarm is raised
against the OPS-LINE port. However, there should be errors logged
against the DS1 Interface circuit pack. Look for DS1-BD/UDS1-BD errors
in the Hardware Error Log, and follow the appropriate procedures provided
in the ‘‘DS1-BD (DS1 Interface Circuit Pack)’’ on page 8-586.
Table 8-484. DS1 OPS Maintenance Error Log Entries
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
0
1
1. Run the short test sequence first. If every test passes, run the long test sequence. Refer to each appropriate
test’s description, and follow its recommended procedures.
0 Any Any Any test station ext
15(a) Any Audit and Update test
(#36)
18(b) 0 busyout station ext WARNING OFF release station ext
130(c) None WARNING ON test station ext
1281 Conference Circuit test
(#7)
MINOR ON test station ext l r 4
1537 NPE Crosstalk test (#6) MINOR ON test station ext l r 3
1793(d) test board UUCSS l