POWER
Issue 1 May 2002
8-1311555-233-143
Battery and Charger for DC-Powered Systems
NOTE:
This MO applies to the J58890CE and the J58890CH-1 with large battery
holdover.
This MO represents the battery backup unit found in AC-powered multicarrier
cabinets. Because the system does not recognize the type of external power, this
MO exists in DC-powered multicarrier cabinets but serves no functional purpose.
In such cabinets, every POWER test should always either pass or abort, and no
POWER alarms should be raised.
S8700 Multi-Connect systems support two different types of PN cabinets:
multicarrier and single-carrier. Both cabinet types may be powered by either AC
or DC external power source. Environmental maintenance differs according to
cabinet type and external power supply.
Error Log Entries and Test to Clear Values
Note:
a. This error occurs is valid only for AC-powered multicarrier cabinets with
battery backup. For DC-powered cabinets, you cannot clear the error and
it should be ignored.
MO’s Name (in
Alarm Log)
Alarm
Level
Initial SAT Command
to Run
1
1. UU is the cabinet number indicated in the PORT field from the Alarm or Error Log.
Full Name of MO
POWER MINOR test environment UU Battery and Battery Charger
Table 8-525. Battery and Battery Charger Error Log Entries
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
0
1
1. Run the short test sequence first. If every test passes, run the long test sequence. Refer to each appropriate
test’s description, and follow its recommended procedures.
0Any Any Anytest environment UU sh r 1
1 Any Battery and Battery Charger
Query test (#5) (error code 8)
MINOR ON test environment UU s r 1
257 Any Battery and Battery Charge
Query test (#5) (error code 4)
MINOR ON test environment UU s r 1
769 Any Battery and Battery Charger
Query test (#5) (error code 2)
MINOR ON test environment UU s r 1
3840 (a) 1005,
1028
Associated Battery and Battery
Charger Query test (#5)
test environment UU s r 1