TIE-TRK (Analog Tie Trunk)
Issue 1 May 2002
8-1651555-233-143
1018 ABORT Test disabled via administration.
1. Verify that the Maintenance Tests? field on the Trunk Group Form is set
to n. To enable the test, issue the change trunk-group x command
where x equals the number of the trunk group to be tested. Then change
the entry in the Maintenance Tests? field on the form to y.
1040 ABORT This test is not performed for trunk ports administered as access endpoints.
1. Verify this port is an access endpoint by using the display port command.
2. If the port has been administered as an access endpoint, then this test
should abort.
2100 ABORT Could not allocate the necessary system resources to run the test. This could
be due to a failure to seize the port.
1. Retry the command at 1-minute intervals up to 5 times.
3 FAIL No dial tone detected from the other end. (TN439 circuit packs only.)
1. Retry the command at one minute intervals up to five times.
2. If the test continues to fail, check the far-end PBX to ensure a translation
match at both ends.
3. Check the facility.
2000 FAIL Seizure message is not received back within 10 seconds.
1. Retry the command at 1-minute intervals up to 5 times.
2. If the test continues to fail, check the far-end PBX to ensure a translation
match at both ends.
3. Check the facility.
PASS The Tie Trunk Seizure test passes. This port is functioning properly.
1. If users are reporting troubles, examine loop connections to the port,
wiring, and stations.
0NO
BOARD
The test could not relate the internal ID to the port (no board).
1. Verify that the boards translations are correct. Translate the board, if
necessary.
2. Issue the busyout board command.
3. Issue the reset board command.
4. Issue the release busy board command.
5. Issue the test board command. This should re-establish the linkage
between the internal ID and the port.
Table 8-642. Test #73,#747 Tie Trunk Seizure Test Continued
Error
Code
Tes t
Result Description / Recommendation
Continued on next page