Maintenance-Object Repair Procedures
555-233-143
8-1882 Issue 1 May 2002
1008 ABORT Could not allocate a ringing circuit for one of the following reasons: all the
ringing circuits are in use; the ringing generator is defective; ringing generator
is not wired correctly.
1. If the test continues to abort, look for RING-GEN error in Error Log.
a. If there are RING-GEN errors, see ‘‘RING-GEN’’ on page 8-1357 and
try to resolve any problem(s). Then, go to step 2.
b. If there are no RING-GEN errors, and the test continues to abort, issue
the test board UUCSS command on other TN742, TN769, or TN746
Analog circuit packs. If an ABORT with error code 1008 occurs for this
test on other circuit packs as well, then the ringing generator may be
defective or may not be wired properly. See ‘‘RING-GEN’’ on page
8-1357 maintenance documentation for details. If an ABORT with error
code 1008 does NOT occur on the other ports, then all four ring
generators are in use. Exit from this documentation.
2. Retry the command.
FAIL No ringing current is detected. The ringing application circuitry on this circuit
pack probably is not healthy.
1. Retry the command again.
2. If the test continues to fail, look for RING-GEN error in Error Log.
a. If there are RING-GEN errors, see ‘‘RING-GEN’’ on page 8-1357 and
try to resolve any problem(s).
b. If there are no RING-GEN errors, then replace the circuit pack.
3. Retry the command again.
PASS Ringing current is detected or this vintage of the Analog Line circuit pack does
not support the Ringing Application Circuit Test. Analog Line circuit packs that
DO NOT support Test #51 include TN712 Vintage 13 and earlier and TN742
Vintage 3 and earlier.
Any NO
BOARD
This is normal if the test is being done when (a) the board is not physically in
the system or (b) the system is booting up. Otherwise, there is some
inconsistency between the physical configuration and the data kept in the
system.
1. Verify that the board is physically in the system.
2. Verify that the system is not in a stage of booting up.
3. Retry the command at 1-minute intervals up to 5 times.