AC-POWER
Issue 1 May 2002
8-11555-233-143
AC Power Query Test (#78)
This test is not valid for DC-powered cabinets and should always abort or pass.
Table 8-4. Test #78 Power Query Test
Error
Code
Tes t
Result Description / Recommendation
1000 ABORT System resources required to run test are not available.
100,
2000
ABORT Response to the test request was not received within the allowable time period.
2029,
2319,
2320,
2500
ABORT Internal system error.
1. Retry the command at 1-minute intervals up to 5 times.
Any FAIL An EPN’s Maintenance circuit pack is incorrectly reporting an AC power
problem. If this test fails, there is a problem with a Maintenance circuit pack.
Replace the suspect circuit pack, and run the test again. (b)
PASS Since this test is invalid for DC-powered cabinets, this result simply indicates
that an EPN’s Maintenance circuit pack is handling this test properly.