4.4
107.36 Inertia of motor
Moment of inertia of the motor. The value displayed is read from motors with an electronic
identification plate and is for information only.
107.37 Temperature sensor type
Two different types of temperature sensor are available for use. If the motor has no elec-
tronic identification plate, the temperature sensor type must be entered.
107.38 Motor flags
The value of this parameter can be changed, if the drive controller isn’t on *).
*) Switched on means that in the Status word parameter Z108.3–, the bit 1 = 1.
If the synchronous motor is operated sensorless, it can be operated with the new param-
eter value immediately. As with the sensorless synchronous machines, the parameter
value for asynchronous machines is effective immediately. If the same value is written to
the parameter, which already is in the parameter, then this writing procedure has no ef
-
fects.
Value Meaning
0 KTY 84
1 Temperature switch or motor protection thermistor (MSKL)
2 PT1000
15 ... 3 Reserved
Bit Meaning
0 0: Motor phase sequence counter-clockwise
1: Phase sequence clockwise
1 0: Synchronous motor
1: Asynchronous motor
15 ... 2 Reserved
preconfigured with 0
DANGER!
If the value is changed, the drive automatically loses the notch position search for the
synchronous motor. After change the user must execute notch position search again,
in order to operate a synchronous motor with encoder without danger.