Programming Guide | VLT® AutomationDrive FC 360
Option Name Description
[45] Latched start reverse The motor starts to run reverse when a
pulse is applied for minimum 4 ms. The
motor stops when stop commands are
given.
[51] External Interlock This function makes it possible to give
an external fault to the drive. This fault is
treated in the same way as an internally
generated alarm.
[55] DigiPot increase Increase signal to the Digital
Potentiometer function described in
parameter group 3-9* Digital Pot. Meter.
[56] DigiPot decrease Decrease signal to the Digital
Potentiometer function described in
parameter group 3-9* Digital Pot. Meter.
[57] DigiPot clear Clear the Digital Potentiometer reference
described in parameter group 3-9* Digital
Pot. Meter.
[60] Counter A (up) Input for increment counting in the SLC
counter.
[61] Counter A (down) Input for decrement counting in the SLC
counter.
[62] Reset Counter A Input for reset of counter A.
[63] Counter B (up) Input for increment counting in the SLC
counter.
[64] Counter B (down) Input for decrement counting in the SLC
counter.
[65] Reset Counter B Input for reset of counter B.
[72] PID error inverse Invert the calculated error from the
Process PID Controller. Available only if
parameter 1-00 Configuration Mode is set
to [6] Surface Winder or [7] Extended PID
Speed OL.
[73] PID reset I part Reset the I-part of the Process PID
Controller. Equivalent to parameter 7-40
Process PID I-part Reset. Available only
when parameter 1-00 Configuration Mode
is set to [6] Surface Winder or [7] Extended
PID Speed OL.
[74] PID enable This option enables the extended Process
PID Controller. Equivalent to parameter
7-50 Process PID Extended PID. Available
only if parameter 1-00 Configuration
Mode is set to [7] Extended PID Speed OL.
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 115