Programming Guide | VLT® AutomationDrive FC 360
Option Name Description
[81] SL digital output B See parameter 13-52 SL Controller Action.
The output goes high whenever the Smart
Logic Action [39] Set dig. out. B high is
executed. The output goes low whenever
the Smart Logic Action [33] Set dig. out. B
low is executed.
[82] SL digital output C See parameter 13-52 SL Controller Action.
The output goes high whenever the Smart
Logic Action [40] Set dig. out. C high is
executed. The output goes low whenever
the Smart Logic Action [34] Set dig. out. C
low is executed.
[83] SL digital output D See parameter 13-52 SL Controller Action.
The output goes high whenever the Smart
Logic Action [41] Set dig. out. D high is
executed. The output goes low whenever
the Smart Logic Action [35] Set dig. out. D
low is executed.
[91] Encoder emulate output A
[95] Power Loss Detection
[160] No alarm The output is high when no alarm is
present.
[161] Running reverse The output is high when the drive is
running counterclockwise (the logical
product of the status bits Running AND
Reverse).
[165] Local ref active
[166] Remote ref active
[167] Start command active The output is high when the drive is
running counterclockwise (the logical
product of the status bits Running AND
Reverse).
[168] Drive in hand mode The output is high when the drive is in
hand-on mode.
[169] Drive in auto mode The output is high when the drive is in
auto-on mode.
[170] Homing Completed The homing operation is completed. This
option is only effective when parameter
37-00 Application Mode is set to [2]
Position Control.
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 123