Option Name Description
[23] Remote, ready, no TW The drive is ready for operation
and is in auto-on mode. There is no
overtemperature warning.
[24] Ready, no over-/under voltage The drive is ready for operation and the
mains voltage is within the specified
voltage range (see the Specifications
section in the design guide).
[25] Reverse The motor runs (or is ready to
run) clockwise when logic = 0 and
counterclockwise when logic = 1. The
output changes as soon as the reversing
signal is applied.
[26] Bus OK Active communication (no timeout) via
the serial communication port.
[27] Torque limit & stop Use in performing a coast stop and in
torque limit condition. If the drive has
received a stop signal and is at the torque
limit, the signal is logic 0.
[28] Brake, no brake warning The brake is active and there are no
warnings.
[29] Brake ready, no fault The brake is ready for operation and there
are no faults.
[30] Brake fault (IGBT) The output is logic 1 when the brake IGBT
is short-circuited. Use this function to
protect the drive if there is a fault on the
brake modules. Use the output/relay to
cut out the mains voltage from the drive.
[31] Relay 123 The relay is activated when [0] Control
Word is selected in parameter group 8-**
Communications and Options.
[32] Mech brake ctrl Enable control of an external mechanical
brake. See parameter group 2-2*
Mechanical Brake for more details.
[36] Control word bit 11
[37] Control word bit 12
[40] Out of ref range This option is active when the actual
speed is outside the settings in parameter
4-54 Warning Reference Low to parameter
4-55 Warning Reference High.
[41] Below reference, low This option is active when the actual
speed is below the speed reference
setting.
126 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360