Option Name Description
[23] Remote, ready, no TW The drive is ready for operation
and is in auto-on mode. There is no
overtemperature warning.
[24] Ready, no over-/under voltage The drive is ready for operation and the
mains voltage is within the specified
voltage range (see the Specifications
section in the design guide).
[25] Reverse The motor runs (or is ready to
run) clockwise when logic = 0 and
counterclockwise when logic = 1. The
output changes as soon as the reversing
signal is applied.
[26] Bus OK Active communication (no timeout) via
the serial communication port.
[27] Torque limit & stop Use in performing a coast stop and in
torque limit condition. If the drive has
received a stop signal and is at the torque
limit, the signal is logic 0.
[28] Brake, no brake warning The brake is active and there are no
warnings.
[29] Brake ready, no fault The brake is ready for operation and there
are no faults.
[30] Brake fault (IGBT) The output is logic 1 when the brake IGBT
is short-circuited. Use this function to
protect the drive if there is a fault on the
brake modules. Use the output/relay to
cut out the mains voltage from the drive.
[31] Relay 123 The relay is activated when [0] Control
Word is selected in parameter group 8-**
Communications and Options.
[32] Mech brake ctrl Enable control of an external mechanical
brake. See parameter group 2-2*
Mechanical Brake for more details.
[36] Control word bit 11
[37] Control word bit 12
[40] Out of ref range This option is active when the actual
speed is outside the settings in parameter
4-54 Warning Reference Low to parameter
4-55 Warning Reference High.
[41] Below reference, low This option is active when the actual
speed is below the speed reference
setting.
126 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals