Programming Guide | VLT® AutomationDrive FC 360
Option Name Description
[170] Homing Completed The homing operation is completed. This
option is only effective when parameter
37-00 Application Mode is set to [2]
Position Control.
[171] Target Position Reached The target position is reached. This option
is only effective when parameter 37-00
Application Mode is set to [2] Position
Control.
[172] Position Control Fault A fault occurred in the positioning
process. Refer to parameter 37-18 Pos.
Ctrl Fault Reason for details about the
fault. This option is only effective when
parameter 37-00 Application Mode is set
to [2] Position Control.
[193] Sleep Mode The drive/system has entered sleep mode.
See parameter group 22-4* Sleep Mode.
[194] Broken Belt Function A broken belt condition has been
detected. See parameter group 22-4*
Sleep Mode.
5-41 On Delay, Relay
Default value: 0.01 s Parameter type: Range (0.00–600.00 s), Array
[2]
Setup: All setups Conversion index: -2
Data type: Uint16 Change during operation: True
Enter the delay of the relay cut-in time. The relay only cuts in if the condition in parameter 5-40 Function Relay is uninterrupted during
the specified time.
Selected
event
Relay
output
Figure 28: On Delay, Relay
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 135