Option Name Description
[73] Logic rule 3 See parameter group 13-4* Logic Rules.
If logic rule 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[74] Logic rule 4 See parameter group 13-4* Logic Rules.
If logic rule 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[75] Logic rule 5 See parameter group 13-4* Logic Rules.
If logic rule 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[80] SL digital output A See parameter 13-52 SL Controller Action.
Output A is low on [32] Smart Logic
Action. Output A is high on [38] Smart
Logic Action.
[81] SL digital output B See parameter 13-52 SL Controller Action.
Output B is low on [32] Smart Logic
Action. Output B is high on [38] Smart
Logic Action.
[82] SL digital output C See parameter 13-52 SL Controller Action.
Output C is low on [32] Smart Logic
Action. Output C is high on [38] Smart
Logic Action.
[83] SL digital output D See parameter 13-52 SL Controller Action.
Output D is low on [32] Smart Logic
Action. Output D is high on [38] Smart
Logic Action.
[95] Power Loss Detection
[160] No alarm The output is high when no alarm is
present.
[161] Running reverse The output is high when the drive is
running counterclockwise (the logical
product of the status bits Running AND
Reverse).
[165] Local ref active
[166] Remote ref active
[167] Start command active The output is high when there is an active
start command, and no stop command is
active.
[168] Drive in hand mode The output is high when the drive is in
hand-on mode.
[169] Drive in auto mode The output is high when the drive is in
auto-on mode.
134 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360