Option Name
[0] No function
[1] Analog Input 53
[2] Analog Input 54
[7] Frequency input 29
[8] Frequency input 33
[11] Local bus reference
[32] Bus PCD
7-46 Process PID Feed Fwd Normal/ Inv. Ctrl.
Default value: [0] Normal Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select for the process PID feedforward normal or inverse control.
Option Name Description
[0] Normal Set the feedforward factor to treat the FF
resource as a positive value.
[1] Inverse Treat the feedforward resource as a
negative value.
7-48 PCD Feed Forward
Default value: 0 Parameter type: Range (0–65535)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Readout parameter where the bus parameter 7-45 Process PID Feed Fwd Resource [32] Bus PCD can be read. The feedforward set from
bus should be in N2 format.
7-49 Process PID Output Normal/ Inv. Ctrl.
Default value: [0] Normal Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select for the process PID output normal or inverse control.
168 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360