Option Name
[0] Disabled
[1] Enabled
9-28 Process Control
Default value: [1] Enable cyclic master Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint16 Change during operation: False
Process control (setting of control word, speed reference, and process data) is possible via either PROFIBUS or standard fieldbus, but not
both simultaneously. Local control is always possible via the LCP. Control via process control is possible via either terminals or fieldbus
depending on the settings in parameter 8-50 Coasting Select to parameter 8-56 Preset Reference Select.
Option Name Description
[0] Disable Disable process control via PROFIBUS
master class 1 and enables process control
via standard fieldbus or PROFIBUS master
class 2.
[1] Enable cyclic master Enable process control via PROFIBUS
master class 1 and disables process
control via standard fieldbus or PROFIBUS
master class 2.
9-44 Fault Message Counter
Default value: 0 Parameter type: Range (0–65535)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Show the number of error events stored in parameter 9-45 Fault Code and parameter 9-47 Fault Number. The maximum buffer capacity
is 8 error events. The buffer and counter are set to 0 after reset or power-up.
9-45 Fault Code
Default value: 0 Parameter type: Range (0–0), Array [64]
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
This buffer contains the alarm word for all alarms and warnings that have occurred since last reset or power-up. The buffer capacity is
maximum 8 error events.
9-47 Fault Number
Default value: 0 Parameter type: Range (0–0), Array [64]
196 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360