Programming Guide | VLT® AutomationDrive FC 360
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
This buffer contains the alarm word for all alarms and warnings that have occurred since last reset or power-up. The buffer capacity is
maximum 8 error events.
9-52 Fault Situation Counter
Default value: 0 Parameter type: Range (0–1000)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Show the number of fault events that have occurred since last reset or power-up.
9-53 Profibus Warning Word
Default value: 0 Parameter type: Range (0–65535)
Setup: All setups Conversion index: 0
Data type: V2 Change during operation: True
Show PROFIBUS/PROFINET communication warnings.
Bit Description
0 Connection with DP master is lost.
1 Not used.
2 FDL (fieldbus data link layer) is not OK.
3 Clear data command received.
4 Actual value is not updated.
5 Baud rate search.
6 PROFIBUS ASIC is not transmitting.
7 Initializing of PROFIBUS is not OK.
8 Drive is tripped.
9 Internal CAN error.
10 Wrong configuration data from PLC.
11 Wrong ID sent by PLC.
12 Internal fault occurred.
13 Not configured.
14 Timeout active.
15 Warning 34 active.
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 197

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals