Programming Guide | VLAutomationDrive FC 360
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
This buffer contains the alarm word for all alarms and warnings that have occurred since last reset or power-up. The buffer capacity is
maximum 8 error events.
9-52 Fault Situation Counter
Default value: 0 Parameter type: Range (0–1000)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Show the number of fault events that have occurred since last reset or power-up.
9-53 Profibus Warning Word
Default value: 0 Parameter type: Range (0–65535)
Setup: All setups Conversion index: 0
Data type: V2 Change during operation: True
Show PROFIBUS/PROFINET communication warnings.
Bit Description
0 Connection with DP master is lost.
1 Not used.
2 FDL (fieldbus data link layer) is not OK.
3 Clear data command received.
4 Actual value is not updated.
5 Baud rate search.
6 PROFIBUS ASIC is not transmitting.
7 Initializing of PROFIBUS is not OK.
8 Drive is tripped.
9 Internal CAN error.
10 Wrong configuration data from PLC.
11 Wrong ID sent by PLC.
12 Internal fault occurred.
13 Not configured.
14 Timeout active.
15 Warning 34 active.
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 197