13-52 SL Controller Action
Default value: [0] Disabled Parameter type: Option, Array [20]
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: True
Select the action corresponding to the SLC event. Actions are executed when the corresponding event (defined in parameter 13-51 SL
Controller Event) is evaluated as TRUE. This is an array parameter containing SLC actions 0 to 19.
Option Name Description
[0] Disabled Select the action corresponding to the
SLC event. Actions are executed when
the corresponding event (defined in
parameter 13-51 SL Controller Event) is
evaluated as true.
[1] No action No action
[2] Select set-up 1 Change the active setup (parameter 0-10
Active Set-up) to 1. If the setup is changed,
it merges with other setup commands
coming from either the digital inputs or
via a fieldbus.
[3] Select set-up 2 Change the active setup (parameter 0-10
Active Set-up) to 2. If the setup is changed,
it merges with other setup commands
coming from either the digital inputs or
via a fieldbus.
[10] Select preset ref 0 Select preset reference 0. If the active
preset reference is changed, it merges
with other preset reference commands
coming from either the digital inputs or
via a fieldbus.
[11] Select preset ref 1 Select preset reference 1. If the active
preset reference is changed, it merges
with other preset reference commands
coming from either the digital inputs or
via a fieldbus.
[12] Select preset ref 2 Select preset reference 2. If the active
preset reference is changed, it merges
with other preset reference commands
coming from either the digital inputs or
via a fieldbus.
[13] Select preset ref 3 Select preset reference 3. If the active
preset reference is changed, it merges
with other preset reference commands
coming from either the digital inputs or
via a fieldbus.