Programming Guide | VLT® AutomationDrive FC 360
Data type: Uint8 Change during operation: True
Select the reset function after tripping. Once reset, the drive can be restarted.
 NOTICE
UNINTENDED START
When the drive is connected to AC mains, DC supply, or load sharing, the motor may start at any time.
Unintended start during programming, service, or repair work can result in death, serious injury, or property
damage. Start the motor with an external switch, a fieldbus command, an input reference signal from the local
control panel (LCP), via remote operation using MCT 10 software, or after a cleared fault condition.
l Disconnect the drive from the mains.
l Press [Off/Reset] on the LCP before programming parameters.
l Ensure that the drive is fully wired and assembled when it is connected to AC mains, DC supply, or load
sharing.
 NOTICE
If the specified number of automatic resets is reached within 10 minutes, the drive enters [0] Manual reset mode. After the manual
reset is performed, the setting of parameter 14-20 Reset Mode reverts to the original selection. If the number of automatic resets is
not reached within 10 minutes, or when a manual reset is performed, the internal automatic reset counter returns to 0.
Option Name Description
[0] Manual reset Select [0] Manual reset to perform a reset
via [Reset] or via the digital inputs.
[1] Automatic reset x 1 Select [1]–[12] Automatic reset x 1…x 20
to perform1–20 automatic resets after
tripping.
[2] Automatic reset x 2
[3] Automatic reset x 3
[4] Automatic reset x 4
[5] Automatic reset x 5
[6] Automatic reset x 6
[7] Automatic reset x 7
[8] Automatic reset x 8
[9] Automatic reset x 9
[10] Automatic reset x 10
[11] Automatic reset x 15
[12] Automatic reset x 20
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 237