Option Name Description
[13] Infinite auto reset Select [13] Infinite Automatic Reset for
continuous resetting after tripping.
[14] Reset at power-up
14-21 Automatic Restart Time
Default value: 10 s Parameter type: Range (0–600 s)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Enter the time interval from trip to start of the automatic reset function. This parameter is active when parameter 14-20 Reset Mode is set
to [1]–[13] Automatic reset.
14-22 Operation Mode
Default value: [0] Normal operation Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: True
Select the operation mode.
Option Name Description
[0] Normal operation Normal operation with motor selected.
[2] Initialisation Reset parameter values to default settings.
The drive resets during the next power-
up.
14-24 Trip Delay at Current Limit
Default value: 60 s Parameter type: Range (0–60 s)
Setup: All setups Conversion index: 0
Data type: Uint8 Change during operation: True
Enter the current limit trip delay in seconds. When the output current reaches the current limit (parameter 4-18 Current Limit), a warning
is triggered. When the current limit warning has been continuously present for the period specified in this parameter, the drive trips. To
run continuously in current limit without tripping, set the parameter to 60 s = Off. Thermal monitoring of the drive remains active.
14-25 Trip Delay at Torque Limit
Default value: 60 s Parameter type: Range (0–60 s)
Setup: All setups Conversion index: 0
Data type: Uint8 Change during operation: True