EasyManua.ls Logo

Danfoss VLT AutomationDrive FC 360

Danfoss VLT AutomationDrive FC 360
340 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Define the maximum error allowed between the actual position and the calculated command position. If the actual error exceeds the
value set in this parameter, the position-control-fault alarm is triggered.
32-68 Reverse Behavior for Slave
Default value: [0] Reversing allowed Parameter type: Option
Setup: All setups Conversion index:
Data type: Uint8 Change during operation: True
Set the reverse behavior.
Option Name
[0] Reversing allowed
[1] Reversing follow master
[2] Reversing blocked
32-69 PID Sample Time
Default value: 16 ms Parameter type: Range (1–1000 ms)
Setup: 1 setup Conversion index: 0
Data type: Uint16 Change during operation: True
PID sample time of position control. Increase the time if the controller is unstable because of a low-resolution feedback signal or very
high load inertia.
32-71 Size of the Control Window (Activation)
Default value: 0 Parameter type: Range (0–1073741823)
Setup: All setups Conversion index: 0
Data type: Uint32 Change during operation: True
Define the size of the control window (activation).
32-72 Size of the Control Window (Deactiv.)
Default value: 0 Parameter type: Range (0–1073741823)
Setup: All setups Conversion index: 0
Data type: Uint32 Change during operation: True
Define the size of the control window (deactivation).
32-73 Integral limit filter time
Default value: 0 ms Parameter type: Range (-10000–10000 ms)
Setup: All setups Conversion index: 0
Data type: Int16 Change during operation: True
284 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLAutomationDrive FC 360

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Related product manuals