Programming Guide | VLT® AutomationDrive FC 360
1-22 Motor Voltage
Default value: Size related Parameter type: Range (50–1000 V)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: False
Enter the nominal motor voltage according to the motor nameplate data. The default value corresponds to the nominal rated output of
the unit.
1-23 Motor Frequency
Default value: Size related Parameter type: Range (5–500 Hz)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: False
Select the motor frequency value from the motor nameplate. For 87 Hz operation with 230/440 V motors, set the value according to the
nameplate data for 230 V/50 Hz. Adapt parameter 4-14 Motor Speed High Limit [Hz] and parameter 3-03 Maximum Reference to the 87
Hz application.
1-24 Motor Current
Default value: Size related Parameter type: Range (0.01–1000.00 A)
Setup: All setups Conversion index: -2
Data type: Uint32 Change during operation: False
Enter the nominal motor current value from the motor nameplate data. This data is used for calculating motor torque, motor thermal
protection, and so on.
1-25 Motor Nominal Speed
Default value: Size related Parameter type: Range (50–60000 RPM)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: False
Enter the nominal motor speed value from the motor nameplate data. This data is used for calculating automatic motor compensations.
1-26 Motor Cont. Rated Torque
Default value: Size related Parameter type: Range (0.1–10000.0 Nm)
Setup: All setups Conversion index: -1
Data type: Uint32 Change during operation: False
Enter the value from the motor nameplate data. The default value corresponds to the nominal rated output. This parameter is available
when parameter 1-10 Motor Construction is set to [1] PM, non salient SPM or [3] PM, salient IPM, that is, the parameter is valid for PM,
non-salient SPM and PM, salient IPM motors only.
1-29 Automatic Motor Adaption (AMA)
Default value: [0] Off Parameter type: Option
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 59

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals