Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: False
The AMA function optimizes dynamic motor performance by automatically optimizing the advanced motor parameters.
 NOTICE
Terminal 27 digital input (parameter 5-12 Terminal 27 Digital Input) has coast inverse as the default setting. This setting means
that AMA cannot be performed if terminal 27 is switched off.
Option Name Description
[0] Off No function.
[1] Enable Complete AMA Depending on the option selected in
parameter 1-10 Motor Construction,
the AMA is performed on different
parameters.
• If [0] Asynchron is selected, the AMA is
performed on:
- Parameter 1-30 Stator Resistance
(Rs)
- Parameter 1-31 Rotor Resistance
(Rr)
- Parameter 1-33 Stator Leakage
Reactance (X1)
- Parameter 1-35 Main Reactance
(Xh)
• If [1] PM, non-salient SPM is selected,
the AMA is performed on:
- Parameter 1-30 Stator Resistance
(Rs)
- Parameter 1-37 d-axis Inductance
(Ld)
• If [3] PM, salient IPM is selected, the
AMA is performed on:
- Parameter 1-30 Stator Resistance
(Rs)
- Parameter 1-37 d-axis Inductance
(Ld)
- Parameter 1-38 q-axis Inductance
(Lq)
- Parameter 1-44 d-axis Inductance
Sat. (LdSat)
- Parameter 1-45 q-axis Inductance
Sat. (LqSat)
60 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360