P No. Index Name Unit Description
344 0 CON_FM_VConTF ms Timeconstantofvoltagecontrolleractualvalue
filter
345 0 CON_FM_VConKp A/V VoltagecontrollergainfactorKp
346 0 CON_FM_VConTn ms Voltagecontrollerintegral-actiontimeTn
347 0 CON_FM_VRef % Voltagecontrollerreference(as%ofthecurrent
DClinkvoltage)Ifthevalue0%isset,the
controllerisnotactive.
458 0 MOT_SNom rpm Motorratedspeed
Table 7.26: “Voltage controller” parameters
NOTE
l Ifthecontrolreserveistoosmall,theServocontrollertypically
shutsoffwithanovercurrenterror.
ID No.: 0842.26B.5-01Date: 09.2020
ServoOne- Device Help
148
7 Control
7.7FieldweakeningandLookUpTable(LUT),
synchronousmotor
LookUp Table, LUT
For better control of motors with a torque reluctance component. For motors with
different inductances on the d and q axis, a reluctance torque can contribute to
obtaining better utilization of the overall torque. The d and q current have feed
forward control in dependence on the target torque and the actual speed by means
of tables (LUT). As this approach also subjects the d component of the current to
feed forward control in exactly the same manner as the field weakening designed to
achieve higher speeds as described below, the LUT usually considers both the
torque and the field weakening simultaneously for the d current.
Field weakening
Synchronous motors can also be operated above their rated speed at rated voltage
by reducing their voltage consumption through the injection of a current component.
Features
l Themethodisrelativelyrobustagainstparameterfluctuations.
l Thevoltagecontrollercanonlyfollowrapidspeedandtorquechangestoa
limiteddegree.
l Anon-optimizedvoltagecontrollermaycauseoscillation;thecontrollermust
beoptimized.