Engineering via SICAM WEB
SICAM RTUs, User Manual SICAM CMIC 195
DC8-001-2.09, Edition 08.2016
Processing type Parameter Meaning
1_out_of_n_t_1 Within this time (in sec) the 1 out of n enabling
must occur on the command.
0 = no 1 out of n enabling necessary.
Attention: Function only active if sync_t = 0.
0.1 to 25.5
Sw_Seq_command_seq_0 Switching sequence: output additional com-
mand before or after the command
Sw_Seq_addtl_com_0 Switching sequence: Select the additional
command
Sw_Seq_command_seq_1 Switching sequence: output additional com-
mand before or after the command
Sw_Seq_addtl_com_1 Switching sequence: Select the additional
command
RS_Mon_Source_0 Source of state information for state infor-
mation monitoring
• Peripherals
• open-/closed loop control function
• both (logical OR)
RS_Mon_Source_1 Source of state information for state infor-
mation monitoring
• Peripherals
• open-/closed loop control function
• both (logical OR)
SID-BSE Source identification basic system element
SID-ST Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254. If
automatic then the source ID will be learned.
SID-SSE Source identification supplementary system
element
QOC>8 If QOC > 8 (Qualifier of Command) is accept-
ed, so all QOC > 8 will be interpreted as
QOC = 0
ON_before_OFF Definition of the order for the wiring of double
commands/double point information:
• NO: OFF is I/O with lower I/O number ON is
I/O with higher I/O number
• YES: ON is I/O with lower I/O number OFF
is I/O with higher I/O number
Regulating_command Use as regulating command (S)
NO/YES
RS_Image Parameter works only with ACP 1703 platform
DO_DC_2POL – double
command output 2-pole
Retry_suppression_T Command retry suppression time in seconds.
Within this time a command with same ad-
dress is discarded without error information (s)
0.1 to 6553.5
output_t_0 Command output time in seconds (S).
Attention: The time comes into effect only, if in
the message is not defined any time.
0.01 to 327.67
select_execute_t Max. time between select and execute (in se-
conds). After this time a recent select com-
mand is necessary.
0 = no select command is expected (direct
command transmission)
0.1 to 102.3