Engineering via SICAM WEB
196 SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
Processing type Parameter Meaning
Sync_t_0 Within this time (in sec) the interlock enabling
must occur on the command.
0 = no syncronisation over interlocking
0.1 to 6553.5
RS_Mon_t Return state information monitoring time in
seconds (S).
0 = no return state information monitoring
0.01 to 655.35
Command_prolong_t Command prolongation time in seconds (S)
0.01 to 327.67
output_t_1 Command output time in seconds (S).
Attention: The time comes into effect only, if in
the message is not defined any time.
0.01 to 327.67
Sync_t_1 Within this time (in sec) the interlock enabling
must occur on the command.
0 = no syncronisation over interlocking
0.1 to 6553.5
RS_outp_same_state_0 Selection of command output and command
confirmation, if return state is already end po-
sition before output.
Attention: only active if RS_mon_t is 0.
Sync_Input_t_0 Within this time (in sec) the enabling over the
syncronisation input must occur on the com-
mand.
0 = no syncronisation over syncronisation in-
put.
Attention: Function only active if sync_t = 0
0.1 to 6553.5
1_out_of_n_t_0 Within this time (in sec) the 1 out of n enabling
must occur on the command.
0=no 1 out of n enabling necessary.
Attention: Function only active if sync_t = 0.
0.1 to 25.5
RS_outp_same_state_1 Selection of command output and command
confirmation, if return state is already end po-
sition before output.
Attention: only active if RS_mon_t is 0.
Sync_Input_t_1 Within this time (in sec) the enabling over the
syncronisation input must occur on the com-
mand.
0 = no syncronisation over syncronisation in-
put.
Attention: Function only active if sync_t = 0
0.1 to 6553.5
1_out_of_n_t_1 Within this time (in sec) the 1 out of n enabling
must occur on the command.
0 = no 1 out of n enabling necessary.
Attention: Function only active if sync_t = 0.
0.1 to 25.5
Sw_Seq_command_seq_0 Switching sequence: output additional com-
mand before or after the command
Sw_Seq_addtl_com_0 Switching sequence: Select the additional
command
Sw_Seq_command_seq_1 Switching sequence: output additional com-
mand before or after the command
Sw_Seq_addtl_com_1 Switching sequence: Select the additional
command