Engineering via SICAM WEB
SICAM RTUs, User Manual SICAM CMIC 197
DC8-001-2.09, Edition 08.2016
Processing type Parameter Meaning
RS_Mon_Source_0 Source of state information for state infor-
mation monitoring
Peripherals
open-/closed loop control function
both (logical OR)
RS_Mon_Source_1 Source of state information for state infor-
mation monitoring
Peripherals
open-/closed loop control function
both (logical OR)
SID-BSE Source identification basic system element
SID-ST Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254. If
automatic then the source ID will be learned.
SID-SSE Source identification supplementary system
element
QOC>8 If QOC > 8 (Qualifier of Command) is accept-
ed, so all QOC > 8 will be interpreted as
QOC = 0
ON_before_OFF Definition of the order for the wiring of double
commands/double point information:
NO: OFF is I/O with lower I/O number ON is
I/O with higher I/O number
YES: ON is I/O with lower I/O number OFF
is I/O with higher I/O number
Regulating_command Use as regulating command (S)
NO/YES
RS_Image Parameter works only with ACP 1703 platform
DO_DX – double-point
information and double
command output
Fail_behav Behavior at failure
keep
terminate
SID-BSE Source identification basic system element
SID-ST Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254. If
automatic then the source ID will be learned.
SID-SSE Source identification supplementary system
element
select_execute_t Max. time between select and execute (in se-
conds). After this time a recent select com-
mand is necessary.
0 = no select command is expected (direct
command transmission)
0 to 6553.5
RS_Image_CASDU1 Address of corresponding return state infor-
mation (S)
0 to 255
RS_Image_CASDU2 Address of corresponding return state infor-
mation (S)
0 to 255
RS_Image_IOA1 Address of corresponding return state infor-
mation (S)
0 to 255
RS_Image_IOA2 Address of corresponding return state infor-
mation (S)
0 to 255
RS_Image_IOA3 Address of corresponding return state infor-
mation (S)
0 to 255

Table of Contents