Chapter 15 — Maintaining the Drives Updating Drive Firmware
November 2016 User GuideSpectra T950 Library
486
Update Using the Update Drive Firmware Utility
TheUpdateDriveFirmwareutilityusesafirmwaretapetoupdateasingle
driveorallofthedrivesinasinglepartition.
Note: YoucannotusetheUpdateDriveFirmwareUtilitytoupdatea
TS11x0technologydrive.
Requirements
Thedrivestobeupdatedmustbeconfiguredinastoragepartition.
Thefirmwareupdatetapemustbeinamagazinestoredinthestorage
partition’sentry/exitpool.
Thedrivesareupdatedonepartitionatatime.
ToupdatethefirmwareofaGlobalSpare,firstsubstitutetheGlobal
Sparedriveforadriveassignedtoapartition.AftertheGlobalSpare
drivecompletesthefirmwareupdateprocess,itcanberemovedfrom
thepartitionandreturnedtothepoolofsparedrives(seeUsethe
GlobalSpareDriveonpage397formoreinformation).
Discontinue Background Operations
Youcannotupdatedrivefirmwareifthelibraryisactivelyrunningany
backgroundoperations,including
MediaAutoDiscovery,
PreScan,and
PostScan.
IfyoudonotwanttowaitforaMediaAutoDiscovery,PreScan,or
PostScanoperationtocomplete,youcanstoptheMediaAutoDiscoveryor
PreScanoperationorpausethePostScanoperation.Forotherbackground
operations,waitfortheprocesstocomplete.
ClickStop Discovery ontheMediaLifecycleManagementToolsscreen
tostopaMediaAutoDiscoveryorPreScanoperation(see
Stopthe
DiscoveryProcessonpage298).
ClickPause PostScanontheMediaLifecycleManagementToolsscreen
topausethePostScanoperationforonehour(see
PausethePostScan
Processonpage307).