Appendix D — Specifications Library Specifications
November 2016 User Guide—Spectra T950 Library
542
Environmental Specifications
Thissectiondescribesenvironmentalspecificationsforthelibrary.Donot
placethelibraryonacarpetedfloororanywhereelsethatposesriskfor
staticdischargethatcoulddamagethelibraryanditsdrives.
Thelibraryisequippedwithinternalfansthatoperateasmuchasis
necessaryforthenumberofDBAsinstalled.Thefanskeepthelibrary’s
internaltemperaturewithinspecificationsaslongasthedatacenter
environmentiswithinspecifications.
Thefollowingtableslistthegeneralenvironmentalspecificationsforthe
library.
The library must be installed on a level, hard-surfaced floor such as cement or tile.
Never install it on carpeted flooring.
When the library is moved from a cold environment to a warm environment, it
should not be powered on for at least 24 hours. This adjustment period prevents
condensation damage.
Operating Environmental Specification
Humidity 20%to80%(non‐condensing)
Humiditygradient Lessthan10%perhour
Ambienttemperature
a
a. The maximum ambient temperature must not exceed 86º F (30º C) when G2 F-QIPs are installed in the
library.
LTO:50°Fto90°F(10°Cto32°C)
TS11x0Technology:61°Fto90°F
(16°Cto32°C)
Maximumtemperaturechangerate
b
b. The temperature and humidity must be allowed to stabilize in the specified ambient environment for
24 hours.
18°Fperhour(10°Cperhour),
non‐condensing
Maximumwetbulbtemperature 77°F(25°C)
Altitude Sealevelto10,000ft(3,048m)
Storing
a
and Shipping (Non-Operating) Environment Specification
a. The library is in its original packaging. The packaging is designed to protect the library from
condensation caused by extreme temperature variations of 27° F (15° C) or more. When the library is
moved from a cold storage environment to a warm operating environment, it must be acclimated in its
packaging for at least 24 hours before opening to prevent serious condensation damage from occurring.
Humidity 10%to95%(non‐condensing)
Temperature –40°Fto149°F(–40°Cto65°C)
Altitude Sealevelto40,000ft(12,192m)