Maintenance
5
Maintenance Procedures
Generator (Optional 10 kW) - Adjust
Adjust hydraulic flow to generator drive motor (1) with
flow control valve (2) to adjust generator speed for an
output frequency of 60 Hz.
Generator (Optional 10 kW) Drive Coupling - Inspect/Replace
Measure clearance between coupler (1) and spider
element (2), and clearance between coupler (3) and
spider element (2). Replace spider element if clearance
exceeds 0.11" (3 mm).
Ground Fault Interrupters - Test
The machine is equipped with ground fault interrupters in each outlet (1) on outlet box for auxiliary
power. The generator must be running to test the ground fault interrupters.
1. Plug in an electrical appliance, preferably a lamp or radio, or use a voltmeter.
2. Start engine and turn on generator. Turn on lamp or radio, or observe voltmeter.
3. Press test button (2) on outlet. Reset button (3)
must pop out immediately and power must go off.
The outlet must be replaced if reset button does not
pop out and power does not go off.
4. Press reset button to reset outlet.
5. Repeat on other outlets.