EasyManuals Logo

YASKAWA A1000 Technical Manual

YASKAWA A1000
628 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #170 background imageLoading...
Page #170 background image
5.2 b: Application
170 YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
PID Block Diagram
Figure 5.26
Figure 5.26 PID Block Diagram
-
+
+
+
+
+
+
+
+
+
1
-1
+
+
+
-
Z
-1
+
-
+
+
+
+
+
Z
-1
-1
Z
-1
Frequency Reference 1 to 16
Frequency Reference
Selection 1
b1-01/15
Option Card
Serial Comm
Terminal A1/A2/A3
Pulse Input
Output
Frequency
P
1/s
b5-08
1
2
3
PID Setpoint
(U5-04)
Proportional Gain
Setting (P)
b5-02
Integral Time
Setting (I)
b5-03
Integral Limit Setting
b5-04
PID Output
Limit/Lower Limit
b5-06 / b5-34
PID Primary Delay
Time Constant
PID disable when:
- b5-01 = 0
- a JOG Command is Input
- PID Disable by Digital Input Enabled
0
PID Integral Hold
H1-
= 31
PID Integral
Reset
H1- = 30
PID Output
Level Selection
b5-09
Enable / Disable Reverse
Operation when PID
Output is Negative
Frequency Reference
PID Target
PID Feedback
0
1
0
1
0
1
0
PID Input
(U5-02)
PID Feedback
(U5-01)
b5-07
b5-10
PID Output
Gain Setting
PID Offset
Adjustment
b5-15
PID Sleep Function Start Level
RUN
On/Off
b5-16
PID Sleep
Delay Time
Sleep Function
SFS
C1-
4
d1-01 to d1-16
H6-01 = 1
b5-05
1 or 3
2 or 4
b5-01
Derivative
Time (D)
not B
b5-05
b5-01
2 or 4
1 or 3
not 1
H3-02/06/10 = B
Terminal A1/A2/A3
Pulse Input
0
PID Input
Limit
b5-35
Disabled
Enabled
Terminal A1/A2/A3
0
not 16
H3-02/06/10
= 16
PID Differential
Feedback
(U5-05)
PID Adjusted
Feedback
(U5-06)
PID Ouput
(U5-03)
Integral Limit
Setting
Upper Limit
Fmax x109%
Lower Limit
Fmax x109%
Lower Limit 0
b5-11
1
0
Upper Limit
Fmax x109%
Always 1 when
b5-01 = 3/4
PID Input
Level Selection
H1-
= 35 or
b5-09
Upper Limit
Fmax x109%
100%
0 50% 100%
d4-11
Bi-directional
Output Sel.
0
1
Bi-directional PID
Ouptut Enable
H1- = 7F
0
1
Always 1
when
PID off
Rev Run
Fwd Run
not 1
b5-18 = 1
Resister, 0FH, bit 1
H6-01 = 2
H3-02/06/10 = C
not C
not 2
0
1
Terminal A1/A2/A3
MEMOBUS Reg. 0006H
Pulse Input
b5-19
On
Off
PID Accel/Decel Time
b5-17
PID Soft Starter Cancel
(H1-
= 34)
0
b5-01 = 3/4
b5-01 = 1/2
PID Function Setting

Table of Contents

Other manuals for YASKAWA A1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA A1000 and is the answer not in the manual?

YASKAWA A1000 Specifications

General IconGeneral
TypeAC Drive
SeriesA1000
Input Voltage200-240V, 380-480V
Frequency Range0-400 Hz
Horsepower Range0.5 to 1000 HP
Power Range0.4 to 630 kW
Control MethodV/f Control
Overload Capacity150% for 60 seconds
BrakingDynamic Braking
CommunicationModbus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Operating Temperature-10 to +50°C
Storage Temperature-20 to 60°C
Humidity5 to 95% RH (non-condensing)
EnclosureIP20

Related product manuals