EasyManuals Logo

YASKAWA A1000 Technical Manual

YASKAWA A1000
628 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #192 background imageLoading...
Page #192 background image
5.3 C: Tuning
192 YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
C5-01, C5-03/C5-02, C5-04: ASR Proportional Gain 1, 2 / ASR Integral Time 1, 2
These parameters can be used to adjust the responsiveness of the ASR.
Note: C5-01 is automatically set when ASR Tuning is performed (T1-01 = 9 or T2-01 = 9).
These parameter settings will function differently depending on the control mode.
V/f Control with PG
Parameters C5-01 and C5-02 determine the ASR characteristics at maximum speed, whereas C5-03 and C5-04 determine
the characteristics at minimum speed.
Figure 5.40
Figure 5.40 ASR Gain and Integral Time in V/fw/PG
CLV, AOLV/PM, and CLV/PM
In these control modes, parameters C5-03 and C5-04 define the ASR gain an integral time at zero speed. The settings in
C5-01 and C5-02 are used at speeds above the setting in C5-07. C5-07 is set to 0 as the default so that C5-01 and C5-02
are used over the entire speed range. Also refer to C5-07: ASR Gain Switching
Frequency on page 193.
Figure 5.41
Figure 5.41 Low-speed and High-speed Gain Settings
The gain set in C5-03 can also be activated with a digital input programmed to “ASR gain switch” (H1- = 77). When
the terminal is open, the drive uses the ASR gain level set by the pattern in the figure above. When the terminal closes,
C5-03 is used. The integral time set to C5-02 is used to change linearly between these settings.
The ASR gain switch command from a multi-function
input terminal overrides the switching frequency set to C5-07.
Figure 5.42
Figure 5.42 ASR Proportional Gain Switch
ASR Gain Tuning (C5-01, C5-03)
The higher this setting, the faster is the speed response. Too high of a setting can lead to oscillation. In general, this
setting should be increased with larger loads in order to minimize the speed deviation.
ASR Integral Time Tuning (C5-02, C5-04)
Determines how fast a continuous speed deviation problem is eliminated. Too long of an integral time makes the speed
control less responsive, while a too short of an integral time can cause oscillation.
No. Parameter Name Setting Range Default
C5-01
ASR Proportional Gain 1
0.00 to 300.00 Determined by A1-02
C5-02
ASR Integral Time 1
0.000 to 10.000 s Determined by A1-02
C5-03 ASR Proportional Gain 2 0.00 to 300.00 Determined by A1-02
C5-04 ASR Integral Time 2 0.000 to 10.000 s Determined by A1-02
E1-04
0
P = C5-03
I = C5-04
P = C5-01
I = C5-02
E1-09
P and I setting
Motor speed
Max. output frequency
Min. output frequency
P, I
P = C5-01
I = C5-02
P = C5-03
I = C5-04
C5-07
Ramp
Motor speed (Hz)
(Low speed)
C5-02 C5-02
OFF
ON
ASR Gain Switch signal
(Digital input)
C5-03 gain setting
Proportional gain (P)
Proportional gain
determined
by motor speed.

Table of Contents

Other manuals for YASKAWA A1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA A1000 and is the answer not in the manual?

YASKAWA A1000 Specifications

General IconGeneral
TypeAC Drive
SeriesA1000
Input Voltage200-240V, 380-480V
Frequency Range0-400 Hz
Horsepower Range0.5 to 1000 HP
Power Range0.4 to 630 kW
Control MethodV/f Control
Overload Capacity150% for 60 seconds
BrakingDynamic Braking
CommunicationModbus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Operating Temperature-10 to +50°C
Storage Temperature-20 to 60°C
Humidity5 to 95% RH (non-condensing)
EnclosureIP20

Related product manuals