5.6 F: Option Settings
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual 233
Parameter Details
5
F6-08: Reset Communication Parameters
Determines whether communication-related parameters (F6-/F7-) are reset when the drive is initialized using
parameter A1-03.
Setting 0: Do not reset parameters F6-/F7- when the drive is initialized with A1-03
Setting 1: Reset F6-/F7- when the drive is ini
tialized with A1-03
Note: F6-08 is not reset when the drive is initialized.
F6-14: bUS Error Auto Reset
Selects whether a bUS error can be automatically reset if automatic fault retry is enabled.
Setting 0: Disabled, Auto Reset Not Possible
Setting 1: Enabled, Aut
o Reset Possible
F7-16: Communication Loss Time Out
Sets the time-out value for communication loss detection in tenths of a second. A value of 0.0 disables the connection
timeout.
Example: A value of “100” represents 10.0 seconds.
CC-Link Parameters
Parameters F6-04, F6-10, and F6-11 set up the drive to operate on a CC-Link network.
For details on parameter settings, refer to the YASKAWA AC
Drive 1000-Series Option CC-Link Installation Manual
and Technical Manual.
MECHATROLINK-II Parameters
Parameters F6-20 through F6-26 set up the drive to operate on a MECHATROLINK-II network.
For details on parameter settings, refer to the YASKA
WA AC Drive 1000-Series Option MECHATROLINK-II
Installation Manual and Technical Manual.
MECHATROLINK-III Parameters
Parameters F6-20, F6-21, F6-23 through F6-26 set up the drive to operate on a MECHATROLINK-III network.
For details on parameter settings, refer to the YASKA
WA AC Drive 1000-Series Option MECHATROLINK-III
Installation Manual and Technical Manual.
PROFIBUS-DP Parameters
Parameters F6-30 through F6-32 and F7-60 through F7-79 set up the drive to operate on a PROFIBUS-DP network.
For details on parameter settings, refer to the YASKAWA
AC Drive 1000-Series Option PROFIBUS-DP Installation
Manual and Technical Manual.
CANopen Parameters
Parameters F6-35 and F6-36 set up the drive to operate on a CANopen network.
For details on parameter settings, refer to the YASKAWA AC
Drive 1000-Series Option CANopen Installation Manual
and Technical Manual.
No. Parameter Name Setting Range Default
F6-08 Reset Communication Parameters 0, 1 0
No. Parameter Name Setting Range Default
F6-14 bUS Error Auto Reset 0, 1 0
No. Parameter Name Setting Range Default
F7-16 Communication Loss Time Out 0.0 to 30.0 s 0.0 s