2.2 Mechanical Installation
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual 51
Mechanical
Installation
2
Note: Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during installation and project
construction. Failure to comply could result in damage to the drive. Place a temporary cover over the top of the drive during
installation. Remove the temporary cover before startup, as the cover will reduce ventilation and cause the drive to overheat.
External/Face-Mount
1. Cut an opening in the enclosure panel for the digital operator as shown in Figure 2.12.
2. Position the digital operator so the display faces outwards, and mount it to the enclosure panel as shown in
Figure 2.11.
Figure 2.11
Figure 2.11 External/Face-Mount Installation
Figure 2.12
Figure 2.12 Panel Cut-Out Dimensions (External/Face-Mount Installation)
Internal/Flush-Mount
An internal flush-mount requires an installation support set that must be purchased separately. Contact your YASKAWA
representative to order an installation support set and mounting hardware. Figure 2.13 illustrates how to attach the
Installation Support Set A.
1.
Cut an opening in the enclosure panel for the digital operator as shown in Figure 2.14.
2. Mount the digital operator to the installation support.
3. Mount the installation support set and digital operator to the enclosure panel.
Figure 2.13
Figure 2.13 Internal/Flush Mount Installation
Note: For
environments with a significant amount of dust or other airborne debris, use a gasket between the enclosure panel and the
digital operator.
Digital Operator
M3 × 6
Phillips recessed
pan head machine screw × 2
Enclosure panel
Unit: mm
22
22
14
26
22
78
2
Unit: mm
Enclosure panel
Unit: mm
Digital Operator
Installation Support Set A
M4 × 10
Phillips truss head screw × 4
(for panel widths between 1 and 1.6)
M3 × 6
Phillips recessed
pan head machine screw × 2

Table of Contents

Other manuals for YASKAWA A1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA A1000 and is the answer not in the manual?

YASKAWA A1000 Specifications

General IconGeneral
TypeAC Drive
SeriesA1000
Input Voltage200-240V, 380-480V
Frequency Range0-400 Hz
Horsepower Range0.5 to 1000 HP
Power Range0.4 to 630 kW
Control MethodV/f Control
Overload Capacity150% for 60 seconds
BrakingDynamic Braking
CommunicationModbus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Operating Temperature-10 to +50°C
Storage Temperature-20 to 60°C
Humidity5 to 95% RH (non-condensing)
EnclosureIP20