C.9 MEMOBUS/Modbus Data Table
564 YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
00C4H
Fault contents 7
bit 0 PID Feedback Loss (FbH)
bit 1 External Fault 1, input terminal S1 (EF1)
bit 2 External Fault 2, input terminal S2 (EF2)
bit 3 Mechanical Weakening Detection 1 (oL5)
bit 4 Mechanical Weakening Detection 2 (UL5)
bit 5 Current Offset Fault (CoF)
bit 6, 7 Reserved
bit 8 DriveWorksEZ Fault (dWFL)
bit 9 EEPROM Memory DriveWorksEZ Data Error (dWF1)
bit A to B Reserved
bit C Output Voltage Detection Fault (voF)
bit D Braking Resistor Fault (rF)
bit E Braking Transistor Overload Fault (boL)
bit F Motor Overheat (NTC Input) (oH5)
00C5H
Fault contents 8
bit 0 LSo Fault (LSo)
bit 1 Node Setup Fault (nSE)
bit 2 Thermistor Disconnect (THo)
bit 3 to 9 Reserved
bit A Polarity Judge Timeout (dv7)
bit B to D Reserved
bit E Power Unit Output Phase Loss 3 (LF3)
bit F Current Unbalance (UnbC)
00C6H
Fault contents 9
bit 0 Gate Drive Board Undervoltage (Uv4)
bit 1 to F Reserved
00C7H Reserved
00C8H
Alarm contents 2
bit 0 Undervoltage (Uv)
bit 1 Drive Overheat Warning (ov)
bit 2 Heatsink Overheat (oH)
bit 3 Drive Overheat Warning (oH2)
bit 4 Overtorque 1 (oL3)
bit 5 Overtorque 2 (oL4)
bit 6 Run Commands Input Error (EF)
bit 7 Drive Baseblock (bb)
bit 8 External Fault 3, input terminal S3 (EF3)
bit 9 External Fault 4, input terminal S4 (EF4)
bit A External Fault 5, input terminal S5 (EF5)
bit B External Fault 6, input terminal S6 (EF6)
bit C External Fault 7, input terminal S7 (EF7)
bit D External Fault 8, input terminal S8 (EF8)
bit E Internal Fan Fault (FAn)
bit F Overspeed (oS)
00C9H
Alarm contents 3
bit 0 Speed Deviation (dEv)
bit 1 PG Disconnected (PGo)
bit 2 External Digital Operator Connection Fault (oPr)
bit 3 MEMOBUS/Modbus Communication Error (CE)
bit 4 Option Communication Error (bUS)
bit 5 Serial Communication Transmission Error (CALL)
bit 6 Motor Overload (oL1)
bit 7 Drive Overload (oL2)
bit 8 Reserved
bit 9 Option Card External fault (EF0)
bit A Motor 2 Switch command input during run (rUn)
bit B Reserved
bit C Serial Communication Transmission Error (CALL)
bit D Undertorque Detection 1 (UL3)
bit E Undertorque Detection 2 (UL4)
bit F MEMOBUS/Modbus Communication Test Mode Error (SE)
Register No. Contents