D.3 UL Standards
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual 593
Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum
allowable temperature of 75C 600 Vac UL-approved vinyl-sheathed insulation.
4A0250
1 2P –
M10
38-L10
YF-1
YET-150-1
TD-224,
TD-212
TP-038 100-051-556
3/0 2P 80-L10
TD-227,
TD-214
TP-080 100-051-557
4/0 2P 100-L10
TD-228,
TD-214
TP-100 100-051-559
250 2P 150-L10
TD-229,
TD-215
TP-150 100-051-561
300 R150-10 TP-150 100-051-272
350
200-10
YF-1
YET-300-1
TD-327,
TD-314
TP-200 100-051-563
400
<1>
500
325-10
TD-328,
TD-315
TP-325 100-051-565
600
4A0296
3/0 2P
M12
80-L12
YF-1
YET-300-1
TD-323,
TD-312
TP-080 100-051-558
4/0 2P 100-L12
TD-324,
TD-312
TP-100 100-051-560
250 2P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 2P
– 350 2P 200-L12
TD-327,
TD-314
TP-200
100-051-564
350 –
R200-12 100-051-275
400
500 <1>
325-12
TD-328,
TD-315
TP-325 100-051-277
600
4A0362
3/0 2P
M12
80-L12
YF-1
YET-300-1
TD-323,
TD-312
TP-080 100-051-558
4/0 2P
<1> 100-L12
TD-324,
TD-312
TP-100 100-051-560
250 2P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 2P
350 2P
200-L12
TD-327,
TD-314
TP-200 100-051-564
400 2P
500
325-12
TD-328,
TD-315
TP-325 100-051-277
600
4A0414
4/0 2P
M12
100-L12
YF-1
YET-300-1
TD-324,
TD-312
TP-100 100-051-560
250 2P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 2P
<1>
4A0515
3/0 4P
<1> 3/0 4P
M12
80-L12
YF-1
YET
-300-1
TD-323,
TD-312
TP-080 100-051-558
4/0 4P 4/0 4P
<1> 100-L12
TD-324,
TD-312
TP-100 100-051-560
250 4P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 2P
4A0675
4/0 4P
M12
100-L12
YF-1
YET
-300-1
TD-324,
TD-312
TP-100 100-051-560
250 4P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 4P
<1>
4A0930
3/0 8P
M12
80-L12
YF-1
YET-300-1
TD-323,
TD-312
TP-080 100-051-558
4/0 8P
<1> 100-L12
TD-324,
TD-312
TP-100 100-051-560
250 8P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 8P
4A1200
4/0 8P
M12
100-L12
YF-1
YET-300-1
TD-324,
TD-312
TP-100 100-051-560
250 8P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 8P
<1>
<1> Recommended wire gauges.
<2> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each
connection.
Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the
user should order two sets of [100-051-272].
Example 2: Models with 4/0 AWG 2P for both input and output require two sets for input terminals and two sets for output terminals,
so the user should order four sets of [100-051-560].
Drive Model
Wire Gauge (AWG, kcmil)
Screw
Size
Crimp Terminal
Model Number
Tool
Insulation Cap
Model No.
Code <2>
R/L1S/L2T/L3 U/T1V/T2W/T3 Machine No. Die Jaw