Ref ID : ADR233B/IM/SI
Rev No. : 05
Page No. : 108 of 479
ADR233B
3.18.9 Program should be started with following command line parameters:
-i <address> IP address of the device
-u <user> user for FTP server
-p <password> password for FTP server
-d <device> device type
-t <path> path to resources
-h show help message
-x <file> create icd file and close the application
Only -t option is required. Rest of the options are optional.
3.18.10 IEC 61850 Configurator - Main Screen
Figure 57: Main Screen of Goose Configurator
3.18.11 Following functions are provided in IEC 61850 Configurator.
• Import Configuration - import configuration of GOOSE interfaces (for publisher and
subscriber) from previously created file
• Export Configuration - export configuration of GOOSE interfaces (for publisher and
subscriber) to file
• Export ICD - export ICD file with current configuration
• Import SCL - import SCL file containing definitions of GOOSE publishers of other devices to
subscribe to
• Exit - close application