ADR233B
8.4.11.5.2 W1 Phase OC (If IEC/ UK Curve is selected)
PROTECTION
CLEAR RECORDS
OUTPUT & LED TEST
GROUP 1
Password protected window for Group 1 setting. i.e.
Equipment Data, Ph Differential, REF, Phase OC, Ground
OC, Residual OC, Sequence OC, Under Voltage, Over
Voltage, V/Hz Protection, Breaker Failure, Thermal Overload
and Through Fault.
Press the Right arrow key () to move to the next option.
Equipments Data
Ph differential
REF
Phase OC
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) select Phase OC.
Press the Right arrow key () to move to the next option.
Phase OC
W1 Phase OC
W2 Phase OC
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) select W1 Phase OC.
Password protected window for W1 Phase OC” setting i.e.
IP>1 Enable, IP>2 Enable and IP>3 Enable can be set as
Disabled/Enabled.
Press the Right arrow key () to move to the next option.
W1 Phase OC
IP>1 Enable
Enabled
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) the IP>1 Enable can be set i.e.
Disabled/Enabled.
Note: When set as Enabled
Press the Right arrow key () to move to the next option.
W1 Phase OC
IP>1 Curve
IEC S Inverse
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) the IP>1 Curve can be set i.e. Definite Time
/ IEC S Inverse / ST Inverse 1.3S / IEC V Inverse / IEC E
Inverse / UK LT Inverse / IEEE M Inverse / IEEE V Inverse /
IEEE E Inverse / US Inverse / US ST Inverse.
Note: When set as IEC Curve.
Press the Minus / Down arrow key (- /) to move to the next
option.