ADR233B
Ground OC
IE>2 Enable
Disabled
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) the IE>2 Enable can be set i.e. Disabled /
Enabled.
Note: When set as Disabled
Press the Minus / Down arrow key (- /) to move to the next
option.
Ground OC
IE>3 Enable
Disabled
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) the IE>3 Enable can be set i.e. Disabled /
Enabled.
Note: When set as Disabled
Press the Right arrow key () to move to the next option.
Press
Key
For SAVE
Press Target Reset
Key For Cancel
Press the Left arrow key () to SAVE the changes.
SAVE SETTINGS
This window will flash for a moment and it will move to the
Main Menu.
PROTECTION
CLEAR RECORDS
OUTPUT & LED TEST
GROUP 1
8.4.11.6.2 Ground OC (If IEC Curve is selected)
PROTECTION
CLEAR RECORDS
OUTPUT & LED TEST
GROUP 1
Password protected window for Group 1 setting. i.e.
Equipment Data, Ph Differential, REF, Phase OC, Ground
OC, Residual OC, Sequence OC, Under Voltage, Over
Voltage, V/Hz Protection, Breaker Failure, Thermal Overload
and Through Fault.