INADS (INADS Link)
Issue 1 May 2002
8-927555-233-143
Table 8-358. INADS Link Test Error Log Entries
Error
Code
Tes t
Result Description / Recommendation
1 0 A test call was successfully placed to the alarm receiver. No trouble found.
2 0 Informative error indicating that alarm origination was disabled at the time of
the test. The test runs even though alarm origination is disabled.
1. If desired, enable Alarm Origination via the Maintenance-Related System
Parameters form.
2. Repeat the test.
3 0 The alarm receiver’s connection is currently in use.
1. Wait 10 minutes, and retry this command.
4 0 The alarm receiver did not answer the test call.
1. Verify that the alarm receiver is up and running.
2. Verify the accuracy of the alarm receiver’s phone number and the system’s
product ID using the Maintenance-Related System Parameters form.
3. Enable alarm origination via the Maintenance-Related System Parameters
form.
Test the SYSAM (System Access Maintenance) by issuing the test
maintenance a | b command.
4. Retry the command.
5 0 The alarm receiver’s phone number is not assigned.
1. Assign the alarm receiver’s phone number via the Maintenance-Related
System Parameters form.
2. Retry the command.
6 0 The alarm receiver did not return an acknowledgment for the “test inads alarm”
message.
1. Verify the accuracy of the alarm receiver’s phone number and the system’s
product ID via the Maintenance-Related System Parameters form.
2. Verify that the alarm receiver is up and running.
3. Retry the command.
7 0 The alarm receiver returned a negative acknowledgment for the “TESTING
INADS LINK” message.
1. Verify that the product IDs match in the customer’s switch and the alarm
receiver’s database. Use the Maintenance-Related System Parameters
form to identify the product ID of the switch.
2. Rerun the test.
Continued on next page