Maintenance-Object Repair Procedures
555-233-143
8-1822 Issue 1 May 2002
m. Error Type 25612668 System software received an indication that the
socket was closed due to an error. Errors are reported as log only. Errors
logged here are for the sockets that had no processor channels associated
with them, for example, sockets to read SNMP data. The counter base is
offset by the application type of the application associated with this socket
that is down. The Aux Data field of the log entry contains this applications
number, for example, a SNMP application would have its application
number in the Aux Data field.
NOTE:
25612668 is a range of reserved numbers for future applications.
2570 currently represents an SNMP socket failure.
n. Error Type 28172819 Congestion Query test (#600) failed.
The Error Types correspond to the descriptions:
1. See ‘‘Congestion Query Test (#600)’’ on page 8-1830 for Abort and
Fail 3601s.
o. Error Type 3073 Remote Socket Control Link (RSCL) or Link Status
test (#601) failed. This failure can be due to:
This circuit pack
The packet bus
The packet interface circuit pack.
p. Error Type 3330 Critical failure in Packet bus interface.
Below, Error Types correspond to descriptions.
1. Attempt to clear the alarm (reset board UUCSS).
2. If alarm persists, replace circuit pack.
2817 Every buffer exhausted.
2819 Utilized buffers exceed threshold.
If: Then:
Active buffers exceed threshold, VAL enters congested state.
If: Then:
RSCL disconnects at link level Link fails
Link cannot be reconnected quickly Switch raises MINOR alarm
If the switch detects: Then it:
1 error, Resets circuit pack.
2 errors in 15 minutes, Raises MINOR alarm.