4.4
52.11 Inertia measured
Display of the measured inertia of the drive (sum of the motor and the load inertia) at the
Ks measurement by accelerating/braking. The inertia is calculated from the measured Ks
Z52.8 and the Kt factor Z107.44.
52.12 Amplitude for FFT
Axis-dependent amplitude for the starting signal of the Ks measurement. When starting
the Ks measurement with FFT this signal is put on the parameter
Z104.12 and starts
the distance via the lsq additional set value (Z19.17).
52.15 Kp identification
Optimized gain of speed controller form the identification.
52.16 Tn identification
Optimized reset time of the speed controller from the identification.
52.17 Phase margin
Setting of the required phase margin which the speed controller was designed to.