Description of the Software Modules and Parameters
Parameter manual b maXX BM3000
Document no.: 5.12001.07
315
of 820
4
170.22 Write event parameter REAL
Writing on this REAL parameter leads to a call of the "Event write REAL" task, if the POU
is enabled via
Z170.3.
170.30 Error code
This parameter shows the PLC specific error code, if an error has occurred during trans-
lation or at the run-time.
Error code Meaning
3000 Error in project – maximum count of tasks exceeded
3001 Error in project – maximum count of program organization units (POU)
exceeded.
3002 Error in project – unknown data type in intermediate code
3003 Error in project – unknown insert mode (assembler header of instruction)
3004 Error in project – bad operator code
3005 Error in project – bad operator code length
3006 Error in project – bad operand. Operand does not match operator
3007 Error in project – data type is not supported for the current operator code
3008 Error in project – bad asm table entry
3009 Error in project – bad parameter id
3010 Error in project – the used parameter is not of scalar type. Arrays and
structures are not supported yet.
3011 Error in project – bracket close instruction without bracket open
3012 Error in project – unknown label in jump instruction
3013 Error in project – unknown POU number in CAL instruction
3014 Error in project – back jump found within a POU which is called from an
interrupt service POU (RT0, RT1, RT2, fieldbus task, etc.).
3015 Code memory overflow
3016 Buffer overflow intermediate code
3017 Invalid accumulator data type
3018 Watchdog error default task
3019 Check operator error (see CHK_ACC or CHK_OPD)
3020 Watchdog error event task
3021 Error in project – not supported task type in project file
3022 The loaded PLC project is not valid for the PLC extension stage of the
controller. The controller is not activated for the full version of the PLC.