Management
Parameter manual b maXX BM3000
Document no.: 5.12001.07 Baumüller Nürnberg GmbH
336
of 820
4.5
4 SWITCHED ON OPERATION ENABLED
n Event:
Drive activation by control word:
m "Enable Operation" command
Drive activation by hardware control inputs:
m Controller Enable input = High (only if Controller Enable (RF) hardware control in-
put is used)
n Condition:
Drive activation by control word:
m Controller Enable input = High (only if Controller Enable (RF) hardware control in-
put is used)
n Action:
m Drive function is enabled
5 OPERATION ENABLED OPERATION INHIBIT ACTIVE
n Event:
m "Inhibit Operation" command or
Drive activation by hardware control inputs:
m Controller Enable input = Low (transition only possible if Controller Enable (RF)
hardware control input is used)
n Action:
m Operation Inhibit is initiated (braked or coast-down, depending on setting)
5a OPERATION INHIBIT ACTIVE SWITCHED ON
n Event:
m INHIBIT response (P108.15) is set to "Inhibit Drive Function" (Pulse Inhibit, value
0) or
m Operation Inhibit has ended (speed 0 reached)
n Action:
m Drive function is inhibited
6 SWITCHED ON READY TO SWITCH ON
n Event:
m "Shut Down" command or
m Pulse enable input = Low
n Action:
m None
7 READY TO SWITCH ON SWITCH-ON INHIBIT
n Event:
m "Quick Stop" command or
m "Inhibit Voltage" command or
m Quick Stop input = Low (only if Quick Stop (SH) hardware control input is used)