Parameter manual b maXX BM3000
Document no.: 5.12001.07 Baumüller Nürnberg GmbH
390
of 820
4.5
At internal transmission this parameter is displayed for diagnostics.
100.9 Error reaction set value
This error code is sent from the other drive. The receiving drive should execute this reac-
tion, if Z100.7– bit 0 = 1 and bit 1 = 1.
At external transmission (fieldbus) the parameter must be mapped cyclically so that it ap-
pears as an actual value on the sending drive and as a set value on the receiving drive.
I.e. the control must copy
Z100.8– of drive 1 to Z100.9– of drive 2.
100.11 Launch application error
The application errors 1 to 5 are set by writing this parameter.
Function Drive 1 Control Drive 2
Transmission exter-
nal
Z100.7– = 1 Z100.9– (Drive 2) =
Z100.8– (Drive 1)
Z100.9– (Drive 1) =
Z100.8– (Drive 2)
Z100.7– = 1
Transmission inter-
nal (within a double
axis)
Z100.7– = 3 - Z100.7– = 3
Value Error, which is set
0 Noneffective
1 175 - Application error 1
2 176 - Application error 2
3 177 - Application error 3
4 178 - Application error 4
5 179 - Application error 5