Set Value Generators
Parameter manual b maXX BM3000
Document no.: 5.12001.07 Baumüller Nürnberg GmbH
440
of 820
4.6
168.6 Increment
Setting the amount of output value change.
If e.g. the value 1% is set, the ramp function generator parameter Z110.5– Input 16 bit
increases by 1% at each clicking of the "Motor potentiometer+" button up to the maximum
upper limit
Z168.4– in the edge sensitive mode.
Increment
int
= Increment Z168.6– [%] / 100% * Max Z110.5–
where Max Z110.5– = 16384 = internal standardization of 100% of the ramp function
generator parameter Z110.5– Input 16 bit
Increment
int
= Increment Z168.6– [%] / 100% * 16384