Description of the Software Modules and Parameters
Parameter manual b maXX BM3000
Document no.: 5.12001.07
99
of 820
4
129.85 Peak current 2 kHz TM
129.86 Peak current 4 kHz TM
129.87 Peak current 8 kHz TM
129.88 Peak current 16 kHz TM
From controller firmware version V01.10 and up:
Maximum admitted current of the power unit at the accordant PWM frequency Z130.15–
The parameter is valid only if the temperature model for the PU overload monitoring is
used (see PU temperature model state
Z175.2– Bit 0)
The value in this parameter is valid for the required operating requirements. See chapter
"Technical data" in the Instruction Handbook.
The currently valid power unit peak current dependent of the entered PWM frequency
Z130.15–, is shown in parameter Z6.25–.
There is no connection between the peak current (>129.85< to >129.88<) and the peak
current time
Z129.22–. The maximum permitted time for the peak current is specified in
chapter "Technical data" of the Instruction Handbook of the device.
130.1 Heat sink temperature
Power Unit Heat Sink Temperature
130.2 Interior temperature
Internal temperature of the device
130.3 DC link voltage
Actual value of the DC link voltage