Commissioning
Ramp rise time
Accelerated and uniform acceleration and deceleration via S-curve. Thereby the jerk
during acceleration and deceleration is reduced. The value is used both for clockwise
and anticlockwise operation. (0 ms)
Torque control
Motorpot. via Digital Inputs
Speed control is switched off when torque control is switched on.
P30 must be set to 410 (asynchronous motor) or 610 (synchronous motor).
Speed control
Optimize speed controller
Amplification 1 (|f|<P738) (10)
Integral Time 1 (|f|<P738) (104 ms)
The Speed Control is always limited by the Minimum Frequency (P418) and Maximum
Frequency (P419).
P30 must be set to 410 (asynchronous motor) or 610 (synchronous motor).
82
Operating Instructions
Agile