Programming Guide | VLT® AutomationDrive FC 360
Option Name Description
[10] Reversing Change the direction of motor shaft
rotation. Select logic 1 to reverse. The
reversing signal only changes the
direction of rotation. It does not activate
the start function. Select both directions
in parameter 4-10 Motor Speed Direction.
The function is not active in process
closed loop.
[11] Start reversing Used for start/stop and for reversing on
the same wire. Signals on start are not
allowed at the same time.
[12] Enable start forward Disengage the counterclockwise
movement and allows clockwise direction.
[13] Enable start reverse Disengage the clockwise movement and
allows counterclockwise direction.
[14] Jog Use to activate jog speed. See parameter
3-11 Jog Speed [Hz].
[15] Preset reference on Shift between external reference and
preset reference. It is assumed that [1]
External/preset has been selected in
parameter 3-04 Reference Function.
Logic 0 = external reference active; logic 1
= 1 of the 8 preset references is active.
[16] Preset ref bit 0 Preset ref. bits 0, 1, and 2 enable the
selection of 1 of the 8 preset references
according to Table 15.
[17] Preset ref bit 1 Same as [16] Preset ref bit 0.
[18] Preset ref bit 2 Same as [16] Preset ref bit 0.
[19] Freeze reference Freeze the actual reference, which is now
the point of enable/condition for [21]
Speed up and [22] Speed down to be used.
If [21] Speed up or [22] Speed down is
used, the speed change always follows
ramp 2 (parameter 3-51 Ramp 2 Ramp Up
Time and parameter 3-52 Ramp 2 Ramp
Down Time) in the range 0–parameter
3-03 Maximum Reference.
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 113