Option Name Description
[0] No operation Default for all digital outputs and relay
outputs.
[1] Control Ready The control card is ready.
[2] Drive ready The drive is ready for operation and
applies a supply signal on the control
board.
[3] Drive rdy/rem ctrl The drive is ready for operation and is in
auto-on mode.
[4] Stand-by/no warning Ready for operation. No start or stop
command is given (start/disable). No
warnings are active.
[5] Running The motor is running and shaft torque is
present.
[6] Running/no warning The motor is running and there are no
warnings.
[7] Run in range/no warn The motor is running within the
programmed current and speed ranges
set in parameter 4-50 Warning Current
Low to parameter 4-51 Warning Current
High. There are no warnings.
[8] Run on ref/no warn The motor runs at reference speed. No
warnings.
[9] Alarm An alarm activates the output.
[10] Alarm or warning An alarm or a warning activates the
output.
[11] At torque limit The torque limit set in parameter 4-16
Torque Limit Motor Mode or parameter
4-17 Torque Limit Generator Mode has
been exceeded.
[12] Out of current range The motor current is outside the range set
in parameter 4-18 Current Limit.
[13] Below current, low The motor current is lower than set in
parameter 4-50 Warning Current Low.
[14] Above current, high The motor current is higher than set in
parameter 4-51 Warning Current High.
[15] Out of frequency range Output frequency is outside the frequency
range.
[16] Below frequency, low The output speed is lower than the setting
in parameter 4-40 Warning Freq. Low.
150 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507