Programming Guide | VLAutomationDrive FC 360
Option Name Description
[63] Comparator 3 See parameter group 13-1* Comparators.
If comparator 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[64] Comparator 4 See parameter group 13-1* Comparators.
If comparator 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[65] Comparator 5 See parameter group 13-1* Comparators.
If comparator 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[70] Logic rule 0 See parameter group 13-4* Logic Rules.
If logic rule 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[71] Logic rule 1 See parameter group 13-4* Logic Rules.
If logic rule 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[72] Logic rule 2 See parameter group 13-4* Logic Rules.
If logic rule 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[73] Logic rule 3 See parameter group 13-4* Logic Rules.
If logic rule 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[74] Logic rule 4 See parameter group 13-4* Logic Rules.
If logic rule 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[75] Logic rule 5 See parameter group 13-4* Logic Rules.
If logic rule 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[80] SL digital output A See parameter 13-52 SL Controller Action.
The output goes high whenever the Smart
Logic Action [38] Set dig. out. A high is
executed. The output goes low whenever
the Smart Logic Action [32] Set dig. out. A
low is executed.
[81] SL digital output B See parameter 13-52 SL Controller Action.
The output goes high whenever the Smart
Logic Action [39] Set dig. out. B high is
executed. The output goes low whenever
the Smart Logic Action [33] Set dig. out. B
low is executed.
[82] SL digital output C See parameter 13-52 SL Controller Action.
The output goes high whenever the Smart
Logic Action [40] Set dig. out. C high is
executed. The output goes low whenever
the Smart Logic Action [34] Set dig. out. C
low is executed.
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 153