CHAPTER 4 PARAMETER
Extended Function Setting Parameter 4-87
4
PA2_67 Alarm detection at undervoltage
No. Name Setting range
Default
value
Change
67
Alarm detection at
undervoltage
0: No detection
1: Detection
1 Power
Select whether or not to detect alarms when undervoltage is detected.
The detected alarms include main power undervoltage.
PA2_69 Deviation detection overflow value
No. Name Setting range
Default
value
Change
69
Deviation detection
overflow value
0.1 to 100.0 [rev] 15.0 Always
Specify the value for detecting an "deviation overflow" alarm.
Enter the parameter in a rotation amount of the motor output shaft.
PA2_70 Overload warning value
No. Name Setting range
Default
value
Change
70 Overload warning value 10 to 100 [%] 50 Always
Specify the output level of the "overload warning (27) signal that is issued as an output signal (OUT
signal).
Use the signal as a warning of an "overload (OL)" alarm.
Characteristics of the overload warning are specified in "CHAPTER 9 CHARACTERISTICS."